136
Advanced Function Setting Level
Section 5-7
• When this parameter is set to ON, the heater burnout alarm is held until
either of the following conditions is satisfied.
a
Heater burnout detection is set to 0.0 A.
b
The power is turned OFF then back ON again (i.e., power is reset).
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, or advanced function setting level
.
Related Parameter
HB ON/OFF (advanced function setting level): Page 135
• This parameter sets hysteresis for heater burnout detection.
Related Parameter
HB ON/OFF (advanced function setting level): Page 135
hbl
Heater Burnout Latch
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “heater burnout detection”
parameter must be set to ON.
Setting range
Default
on
: Enabled,
off
: Disabled
off
Function
Setting
See
See
hbh
Heater Burnout Hysteresis
The “heater burnout” parameter must
be set to ON.
The “heater burnout latch” parameter
must be set to OFF.
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
Setting range
Unit
Default
0.1 to 50.0
A
0.1
Function
Setting
See
See
■
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...