![Omron E5AZ User Manual Download Page 162](http://html.mh-extra.com/html/omron/e5az/e5az_user-manual_744338162.webp)
139
Advanced Function Setting Level
Section 5-7
• In the operation level or adjustment level, the display automatically
returns to the PV/SP if there are no key operations for the time set for this
parameter.
• The automatic display return time is disabled when the parameter is set to
OFF. (In that case, the display will not be automatically switched.)
• When a parameter is set to ON, once the alarm function has turned ON it
is held until the power is turned OFF. The latch can be canceled, how-
ever, by switching to the initial setting level, communications setting level,
or
advanced function setting level.
• If alarm outputs are set to “close in alarm,” the outputs are kept closed. If
they are set to “open in alarm,” they are kept open.
Related Parameters
Alarm value 1 to 3: Page 101 to 102, Alarm value upper limit 1 to 3: Page 103
to 104, Alarm value lower limit 1 to 3: Page 103 to 104 (operation level)
Alarm 1 to 3 type (initial setting level): Page 124 to 126
Standby sequence reset: Page 133, Alarm 1 to 3 open in alarm: Page 134,
Alarm 1 to 3 hysteresis: Page 135 (advanced function setting level)
ret
Automatic Display Return Time
Setting range
Unit
Default
OFF, 1 to 99
Second
off
Function
Setting
a1lt
Alarm 1 Latch
Alarm 1 must be assigned, and the
alarm 1 type must not be 0.
a2lt
Alarm 2 Latch
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
a3lt
Alarm 3 Latch
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range
Default
on
: Enabled,
off
: Disabled
off
Function
Setting
See
See
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...