170
Appendix A
Protect Level
Communications Setting Level
Control Output 1
Assignment
out1
When control output 1 is a
pulse output (See note.):
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
none
o
c-o
alm1
alm2
alm3
O
None
When control output 1 is a lin-
ear output (See note.):
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
none
o
c-o
Alarm Output
1
Assignment
alm1
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
none
o
c-o
alm1
alm2
alm3
ALM1
None
Alarm
Output 2
Assignment
alm2
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
none
o
c-o
alm1
alm2
alm3
ALM2
None
Alarm Output
3
Assignment (E5AZ /
E5EZ Only)
alm3
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
none
o
c-o
alm1
alm2
alm3
ALM3
None
Character Select
csel
OFF, ON
off
,
on
ON
None
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
Set value
Operation/Adjust-
ment Protect
oapt
0 to 3
0
None
Initial Setting/Com-
Munications Protect
icpt
0 to 2
1
None
Setting Change Pro-
tect
wtpt
OFF, ON
off
,
on
OFF
None
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
Set value
Protocol Setting
psel
CompoWay/F (SYSWAY),
Modbus (See note.)
cwf
,
mod
Compo-
Way/F
(SYSWAY)
None
Communications
Unit No.
u-no
0 to 99
1
None
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
Set value
Note
The setting range depends on whether control output 1 is a linear output or pulse output.
When setting CWF, either CompoWay/F or SYSWAY can be used as the communications protocol.
(CompoWay/F and SYSWAY are automatically identified by the command frames.)
Note
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...