152
Appendix A
HB and HS Alarms (for Controller with Heater Burnout and HS Alarms)
Note
(1) When the control output 1 ON time is less than 190 ms, heater burnout detection and heater current
measurement are not performed.
(2) When the control output 1 OFF time is less than 190 ms, HS alarm and leakage current measure-
ment are not performed.
Characteristics
Max. heater current
50 A AC
Input current indication accuracy
±
5% FS
±
1 digit max.
Heater burnout alarm setting
range
0.1 to 49.9 A (in units of 0.1A)
0.0 A:
Heater burnout alarm output turns OFF.
50.0 A:
Heater burnout alarm output turns ON.
Min. detection ON time: 190 ms (See note 1.)
HS alarm setting range
0.1 to 49.9 A (in units of 0.1A)
0.0 A:
HS alarm output turns ON.
50.0 A:
HS alarm output turns OFF.
Min. detection OFF time: 190 ms (See note 2.)
Indication accuracy
(ambient temperature of
23
°
C)
Thermocouple (See note 1.):
E5CZ/AZ/EZ: (
±
0.5% of indication value or
±
1
°
C, whichever is greater)
±
1 digit max.
E5CZ-U:
(
±
1% of indication value or
±
2
°
C, whichever is greater)
±
1 digit max.
Platinum resistance thermometer:
(
±
0.5% of indication value or
±
1
°
C, whichever is greater)
±
1 digit max.
Analog input:
±
0.5% FS
±
1 digit max.
CT input:
±
5% FS
±
1 digit max.
Temperature variation
influence (See note 2.)
Thermocouple (R, S, B)
(±1% of PV or ±10
°
C, whichever is greater) ±1 digit max. (E5CZ)
(±2% of PV or ±10
°
C, whichever is greater) ±1 digit max. (E5CZ-U)
Other thermocouples:
(±1% of PV or ±4
°
C, whichever is greater) ±1 digit max. (E5CZ)
(±2% of PV or ±4
°
C, whichever is greater) ±1 digit max. (E5CZ-U)
*K thermocouple at
−
100
°
C max:
±
10
°
C max.
Platinum resistance thermometer:
(±1% of PV or ±2
°
C, whichever is greater) ±1 digit max.
Analog input:
±1% FS ±1 digit max. (See note 2.)
Voltage variation influence
(See note 2.)
Hysteresis
Controllers with Thermocou-
ple/Resistance Thermome-
ter Universal-inputs
0.1 to 999.9
°
C or
°
F)
(in units of 0.1
°
C or
°
F) (See note 3.)
Controllers with Analog
Inputs
0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Controllers with Thermocou-
ple/Resistance Thermome-
ter Universal-inputs
0.1 to 999.9
°
C or
°
F)
(in units of 0.1 EU) (See note 3.)
Controllers with Analog
Inputs
0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 3,999 s (in units of 1 s)
Derivative time (D)
0 to 3,999 s (in units of 1 s)
Control Period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%)
Alarm setting range
−
1,999 to 9,999 (decimal point position depends on input type)
Sampling period
250 ms
Affect of signal source resis-
tance
Thermocouple:0.1
°
C/
Ω
max.(100
Ω
max.)(See note 4.)
Platinum resistance thermometer:0.4
°
C/
Ω
max.(10
Ω
max.)
Insulation resistance
20 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction vibration
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y and Z directions
Vibration resistance
10 to 55 Hz, peak height amplitude of 0.75 mm for 2 hr each in X, Y, and Z directions
Malfunction shock
100 m/s
2
, 3 times each in X, Y, and Z directions
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...