Output Adjustment Functions
Section 4-14
4-14 Output Adjustment Functions
4-14-1 Output Limits
• Output limits can be set to control the output using the upper and lower
limits to the calculated MV.
• The following MV takes priority over the MV limits.
Manual MV
• For heating/cooling control, upper and lower limits are set of overall heat-
ing/cooling control. (They cannot be set separately for heating/cooling.)
0%
100%
Output
MV upper limit
MV lower limit
O
u
tp
u
t
MV lower limit
MV
u
pper limit
He
a
ting MV
Cooling MV