38
Setting Output Specifications
Section 3-5
3-5-3
Assigned Output Functions
• Function assignments can be changed by changing the settings for con-
trol and alarm assignments.
• The default function assignments for each output are shown below.
• Each output is automatically initialized as shown below by changing the
control mode.
Example: E5CZ
Note
For the E5AZ/EZ, alarm 3 is assigned for control output (cooling) (alarm output
2 is assigned for alarm 2).
In this manual, assigned control outputs and alarm outputs are indicated as
follows: “Control output 1 must be assigned” or “Alarm 1 must be assigned.”
Operating Procedure
The following example sets the following control and alarm assignments.
Control output 1: Control output (heating); Alarm output 1: Alarm 1; Alarm out-
put 2: Control output (cooling).
5.
Select the “direct/reverse operation” parameter by pressing the
M
key.
The default is
or-r
(reverse operation). To select
or-d
(direct opera-
tion), press the
U
key.
Operation Level
6.
To return to the operation level, press the
O
key for at least one second.
orev
or-r
Direct/reverse
operation
C
30
0
PV/SP
Parameter name
Symbol
Initial status
Control output 1 assignment
out1
Control output (heating)
Alarm output 1 assignment
alm1
Alarm 1
Alarm output 2 assignment
alm2
Alarm 2
Alarm output 3 assignment (E5AZ/
EZ only)
alm3
Alarm 3
Parameter name
Symbol
Standard
Heating/cooling
Control output 1
assignment
out1
Control output (heating)
Control output (heating)
Alarm output 1
assignment
alm1
Alarm 1
Alarm 1
Alarm output 2
assignment
alm2
Alarm 2 (See note.)
Control output (cooling) (See note.)
Operation Level
1.
Press the
O
key for at least 3 seconds to move from the operation level
to the initial setting level.
Initial Setting Levell
Initial Setting Level
2.
Select the “standard or heating/cooling” parameter by pressing the
M
key.
C
25
100
PV/SP
in-t
5
Input type
5-hc
stnd
Standard or
heating/cooling
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...