164
Appendix A
Adjustment Level
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
Set value
AT Execute/Cancel
at
OFF, ON
off
,
on
OFF
None
Communications
Writing
cmwt
OFF, ON
off
,
on
OFF
None
Heater Current 1
Value Monitor
ct1
0.0 to 55.0
A
Leakage Current 1
Monitor
lcr1
0.0 to 55.0
A
Heater Burnout
Detection 1
hb1
0.0 to 50.0
0.0
A
HS Alarm 1
hs1
0.0 to 50.0
50.0
A
SP 0
sp-0
SP lower limit to SP upper
limit
0
EU
SP 1
sp-1
SP lower limit to SP upper
limit
0
EU
SP 2
sp-2
SP lower limit to SP upper
limit
0
EU
SP 3
sp-3
SP lower limit to SP upper
limit
0
EU
Temperature Input
Shift
ins
−
199.9 to 999.9
0.0
°
C or
°
F
Upper-Limit Temper-
ature Input Shift
Value
insh
−
199.9 to 999.9
0.0
°
C or
°
F
Lower-Limit Temper-
ature Input Shift
Value
insl
−
199.9 to 999.9
0.0
°
C or
°
F
Proportional Band
p
Universal-input: 0.1 to 999.9
8.0
°
C or
°
F
(See note.)
Analog input: 0.1 to 999.9
10.0
%FS
Integral Time
i
0 to 3,999
233
Second
Derivative Time
d
0 to 3,999
40
Second
Cooling Coefficient
c-sc
0.01 to 99.99
1.00
None
Dead Band
c-db
Universal-input:
−
199.9 to
999.9
0.0
°
C or
°
F
(See note.)
Analog input:
−
19.99 to 99.99
0.00
%FS
Manual Reset Value
of-r
0.0 to 100.0
50.0
%
Hysteresis (Heating)
hys
Universal-input: 0.1 to 999.9
1.0
°
C or
°
F
(See note.)
Analog input: 0.01 to 99.99
0.10
%FS
Hysteresis (Cooling)
chys
Universal-input: 0.1 to 999.9
1.0
°
C or
°
F
(See note.)
Analog input: 0.01 to 99.99
0.10
%FS
SP Ramp Set Value
sprt
OFF or 1 to 9,999
off
,
1
to
9999
OFF
EU/s, EU/
min
MV Upper Limit
ol-h
MV lower limit +0.1 /105.0
(standard)
0.0 to 105.0 (heating/cooling)
105.0
%
MV Lower Limit
ol-l
−
5.0 to MV upper limit
−
0.1
(standard)
−
105.0 to 0.0 (heating/cool-
ing)
−
5.0 (stan-
dard)
−
105.0
(heating/
cooling)
%
Note
Set “none” as the unit for Controllers with Analog Inputs.
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...