Using Event Inputs
Section 4-5
4-5-3
Settings
Switching between Set Points 0, 1, 2, and 3
Operating Procedure
The following example sets the “number of multi-SP uses” parameter to 2.
Set points 0, 1, 2 and 3 will be set according to the ON/OFF states of event
inputs 1 and 2.
Operation Level
1.
Press the
O
key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2.
Select the “move to advanced function setting level” parameter by press-
ing the
M
key.
3.
Use the
D
key to enter “
−
169” (the password).
Advanced Function Setting Level
Move to the advanced function setting level by pressing the
M
key or
leaving the setting for at least two seconds.
Number of Multi-SP Uses Setting
4.
Select the “number of multi-SP uses” parameter by pressing the
M
key.
5.
Use the
U
key to set the parameter to 2.
6.
To return to the initial setting level, press the
O
key for at least one sec-
ond.
7.
To return to the operation level, press the
O
key for at least one second.
C
25
100
PV/SP
in-t
5
Input type
amov
-169
init
off
Parameter
initialization
ev-m
1
Number of
multi-SP uses
ev-m
2
E5CZ
EV2
EV2
EV1
EV1
−
+
+
E5AZ/EZ
EV2
EV1
EV2
EV1
−
+
+
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...