121
Initial Setting Level
Section 5-6
• These parameters can be used when the input type is set for an analog
input.
• When an analog input is used, scaling is performed. Set the upper limit in
the “scaling upper limit” parameter and the lower limit in the “scaling lower
limit” parameter.
• The “decimal point” parameter specifies the decimal point position of
parameters (set point, etc.) whose unit is EU.
• Scaling Upper Limit, Scaling Lower Limit
• Decimal Point
Related Parameters
Input type (initial setting level): Page 119
• Set the temperature input unit to either
°
C or
°
F.
Related Parameters
Input type (initial setting level): Page 119
in-h
Scaling Upper Limit
The input type must be set for an
analog input.
in-l
Scaling Lower limit
dp
Decimal Point
Parameters
Setting range
Unit
Default
Scaling upper limit
Scaling lower limit + 1 to 9999
None
100
Scaling lower limit
−
1999 to scaling upper limit
−
1
None
0
Parameters
Model
Setting
range
Default
Decimal Point
Controllers with Thermocouple/Resis-
tance Thermometer Universal-inputs
0 to 1
0
Controllers with Analog Inputs
0 to 3
0
Set value
Settings
Example
0
0 digits past decimal point
1234
1
1 digits past decimal point
123.4
2
2 digits past decimal point
12.34
3
3 digits past decimal point
1.234
Function
Setting
See
See
d-u
Temperature Unit
The input type must be set for a tem-
perature input.
Setting range
Default
c
:
°
C,
f
:
°
F
c
Function
Setting
See
See
■
■
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...