25
Wiring Terminals
Section 2-2
ALM 1, 2, 3 can be output to alarm output 1, 2, 3, or changed with the ad-
vanced function setting level.
• The relay specifications are as follows:
CT Inputs
• When the HB alarm or the HS alarm is to be used with the E5CZ-
@
2M
@@
with E53-CZH03 or E53-CZHB, connect a current transformer (CT1)
across terminals 14 and 15 (no polarity).
• When the HB alarm or the HS alarm is to be used with the E5AZ/EZ-
@
3H
@@@
, connect a current transformer (CT1) across terminals 14 and
15 (no polarity).
Event Inputs
• When event inputs are to be used with the following models, connect to
terminals 11 to 13. Option unit with two event inputs is required to be
mounted.
• Use event inputs under the following conditions:
• The outflow current is approximately 7 mA.
Polarities during no-contact input are as follows:
E5CZ/CZ-U
SPST-NO 250 VAC 1 A
E5AZ/EZ
SPST-NO 250 VAC
2
A
E5CZ
E5CZ-U
ALM2
ALM1, HB alarm/HS
alarm, input error
ALM1, input error
ALM2
ALM3
ALM2
ALM1, HB alarm/HS alarm,
input error
E5AZ/EZ
E5CZ-
@
2M
@@
with
E53-CZH03
15
14
CT1
CT1
E5AZ/EZ-
@
3H
@@@
or E53-CZHB
Contact input
ON: 1 k
Ω
max., OFF: 100 k
Ω
min.
No-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current
0.1 mA max.
or
E53-CZHB
M
M
M
Summary of Contents for E5AZ
Page 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Page 3: ...iv ...
Page 23: ...xxiv ...
Page 53: ...30 Using the Support Software Port Section 2 3 ...
Page 79: ...56 Using HB and HS Alarms Section 3 10 ...
Page 115: ...92 Output Adjustment Functions Section 4 14 ...
Page 173: ...150 Communications Setting Level Section 5 8 ...
Page 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...