274
Serial Communications
Section 6-3
Procedure
The Serial PLC Links operate according to the following settings in the PLC
Setup.
Settings at the Polling Unit
1,2,3...
1.
Set the serial communications mode of the RS-232C communications port
to Serial PLC Links (Polling Unit).
2.
Set the link method to the Complete Link Method or Polling Unit Link Meth-
od.
3.
Set the number of link words (up to 10 words for each Unit).
4.
Set the maximum unit number in the Serial PLC Links (1 to 7).
Settings at the Polled Units
1,2,3...
1.
Set the serial communications mode of the RS-232C communications port
to Serial PLC Links (Polled Unit).
2.
Set the unit number of the Serial PLC Link Polled Unit.
PLC Setup
Settings at the Polling Unit
Note Automatically allocates 10 words (A hex) when the default setting of 0 hex is
used.
Settings at the Polled Unit
Note The default baud rate is 38.4 kbps
Item
PLC address
Set value
Default
Refresh timing
Word
Bit
RS-232C
port setting
Serial communica-
tions mode
160
11 to 08
8 hex: Serial PLC Links
Polling Unit
0 hex
Every cycle
(except immediate
refresh when exe-
cuting the
STUP(237) instruc-
tion)
Port baud rate
161
07 to 00
00 hex: Standard
0A hex: High-speed
00 hex
Link method
166
15
0: Complete links
1: Polling Unit links
0
Number of link
words
07 to 04
1 to A hex
0 hex (See
note.)
Highest unit num-
ber
03 to 00
0 to 7 hex
0 hex
Item
PLC address
Set value
Default
Refresh timing
Word
Bit
RS-232C
port set-
tings
Serial communica-
tions mode
160
11 to 08
7 hex: Serial PLC Link
Polled Unit
0 hex
Every cycle
(except immediate
refresh when exe-
cuting the
STUP(237) instruc-
tion)
Port baud rate
161
07 to 00
00 hex: Standard
0A hex: High-speed
00 hex
(See note.)
Polled Unit unit
number
167
03 to 00
0 to 7 hex
0 hex
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...