322
Trial Operation and Debugging
Section 7-2
has been completed, the Online Editing Processing Flag (A20111) will turn
OFF.
Online editing can also be temporarily disabled by turning ON the Online Edit-
ing Disable Bit (A52709) while online editing is being performed. Here too, the
Online Editing Wait Flag (A20110) will turn ON.
If a second request for online editing is received while the first request is on
standby, the second request will not be recorded and an error will occur.
Online editing can also be disabled to prevent accidental online editing. As
described above, disable online editing by turning ON the Online Editing Dis-
able Bit (A52709) and setting the Online Editing Disable Bit Validator (A52700
to A52707) to 5A.
Enabling Online Editing from a Programming Device
When online editing cannot be enabled from the program, it can be enabled
from the CX-Programmer.
1,2,3...
1.
Performing Online Editing with a Programming Console
If online editing is executed from a Programming Console and the online
editing standby status cannot be cleared, the Programming Console will be
locked out and Programming Console operations will not be possible.
In this case, connect the CX-Programmer to another serial port and turn
OFF the Online Edit Disable Bit (A52709). The online editing will be pro-
cessed and Programming Console operations will be possible again.
2.
Performing Online Editing with the CX-Programmer
If operations continue with online editing in standby status, CX-Program-
mer may go offline. If this occurs, reconnect the computer to the PLC and
turn OFF the Online Edit Disable Bit (A52709).
Related Auxiliary Bits/Words
Turning OFF Outputs
If the Output OFF Bit (A50015) is turned ON through the OUT instruction or
from a Programming Device, all outputs from all Output Units will be turned
OFF (this applies to the built-in general-purpose or pulse outputs on CJ1M
CPU Units as well), and the INH indicator on the front of the CPU Unit will turn
ON.
The status of the Output OFF Bit is maintained even if power is turned OFF
and ON.
Name
Address
Description
Online Edit Disable Bit Validator
A52700 to
A52707
Validates the Online Edit Disable Bit (A52709).
Not 5A: Online Edit Disable Bit invalid
5A:
Online Edit Disable Bit valid
Online Edit Disable Bit
A52709
To disable online editing, turn this bit ON and set the Online Edit Disable
Bit Validator (A52700 to A52707) to 5A.
Online Editing Wait Flag
A20110
ON when an online editing process is on standby because online editing
is disabled.
Online Editing Processing Flag
A20111
ON when an online editing process is being executed.
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...