![Omron CJ1G-CPU series Programming Manual Download Page 60](http://html1.mh-extra.com/html/omron/cj1g-cpu-series/cj1g-cpu-series_programming-manual_742489060.webp)
39
Basic Concepts
Section 2-1
• When a word operand is specified for an instruction, I/O will be refreshed
for the 16 bits that are specified.
• Inputs will be refreshed for input or source operand just before an instruc-
tion is executed.
• Outputs will be refreshed for outputs or destination (D) operands just after
an instruction is execute.
Add an exclamation mark (!) (immediate refresh option) in front of the instruc-
tion.
Units Refreshed for I/O REFRESH Instruction
Note C200H I/O Units cannot be mounted to CJ-series PLCs.
Location
CPU or Expansion I/O Rack (but not SYSMAC BUS Slave Racks)
Units
Basic I/O Units
CS/CJ-series Basic I/O
Units
Refreshed
C200H Basic I/O Unit (See
note.)
Refreshed
C200H Group-2 High-den-
sity I/O Units (See note.)
Not refreshed
Special I/O Units
Not refreshed
Top
.
.
.
!LD 000101
.
.
.
!OUT 000209
.
.
.
END
Top
.
.
.
!MOV
0003
0004
.
.
.
END
Input
Output
S
D
CIO 0001
CIO 0002
15
0
15
0
CIO 0003
CIO 0004
15
0
15
0
All real I/O
Immediate refresh
16-bit units
I/O refresh
Cyclic refresh
(batch processing)
16-bit units
I/O refresh
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...