10
Operating Modes
Section 1-4
1-4-2
Initialization of I/O Memory
The following table shows which data areas will be cleared when the operat-
ing mode is changed from PROGRAM mode to RUN/MONITOR mode or
vice-versa.
Note
1.
Non-held areas: CIO Area, Work Area, Timer PVs, Timer Completion
Flags, Index Registers, Data Registers, Task Flags, and Condition Flags.
(The statuses of some addresses in the Auxiliary Area are held and others
are cleared.)
2.
Held areas: Holding Area, DM Area, EM Area, Counter PVs, and Counter
Completion Flags.
3.
Data in I/O memory will be retained when the IOM Hold Bit (A50012) is ON.
When the IOM Hold Bit (A50012) is ON and operation is stopped due to a
fatal error (including FALS(007)), the contents of I/O memory will be re-
tained but outputs on Output Units will all be turned OFF.
Mode change
Non-held Areas
(Note 1)
Held Areas
(Note 2)
RUN/MONITOR
→
PROGRAM
Clear (Note 3)
Retained
PROGRAM
→
RUN/MONITOR
Clear (Note 3)
Retained
RUN
↔
MONITOR
Retained
Retained
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...