281
Changing the Timer/Counter PV Refresh Mode
Section 6-4
• The differences between the CX-Programmer and Programming Console
operations when an incorrect timer/counter PV refresh mode instruction is
input are as follows:
• CX-Programmer:
An error will occur if an instruction is input for a different mode than that
set as the timer/counter PV refresh mode under PLC properties.
Example: When the PLC in the project is set to binary mode, an error
will occur if TIM is input as the mnemonic. When BCD mode is set, an
error will occur if TIMX is input as the mnemonic.
• Programming Console:
When a function code is input for an instruction for a different mode
that for the timer/counter PV refresh mode set in the CPU Unit, the
mnemonic will automatically be changed to that for the timer/counter
PV refresh mode set in the CPU Unit.
6-4-6
Instructions and Operands
Instructions
Instruction
type
Name
Mnemonic
BCD mode
Binary mode
Timer and
Counter
Instructions
TIMER (100 ms)
TIM
TIMX(550)
HIGH-SPEED
TIMER (10 ms)
TIMH(015)
TIMHX(551)
ONE-MS TIMER
(1 ms)
TMHH(540)
TMHHX(552)
ACCUMULATIVE
TIMER (100 ms)
TTIM(087)
TTIMX(555)
LONG TIMER
(100 ms)
TIML(542)
TIMLX(553)
MULTI-OUTPUT
TIMER (100 ms)
MTIM(543)
MTIMX(554)
COUNTER
CNT
CNTX(546)
REVERSIBLE
COUNTER
CNTR(012)
CNTRX(548)
RESET TIMER/
COUNTER
CNR(545)
CNRX(547)
Block pro-
gram instruc-
tions
TIMER WAIT (100
ms)
TIMW(813)
TIMWX(816)
HIGH-SPEED
TIMER WAIT (10 ms)
TMHW(815)
TMHWX(817)
COUNTER WAIT
CNTW(814)
CNTWX(818)
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...