190
File Memory
Section 5-1
3.
One example of the CPU Bus Unit settings would be the Data Link Tables.
Refer to the operation manuals for specific Units for other setup data.
Backup Files (Not
Supported by CS-series
CS1 CPU Units That Are
Pre-EV1)
The files in the following table are created automatically when data is trans-
ferred to and from the Memory Card during backup operation.
Note
1.
Make sure the names of the files used for backup are BACKUP
@@
.
2.
The CIO Area, WR Area, Timer/Counter Completion Flags and PVs, and
force-set/force-reset data that is read from the Memory Card at startup will
be cleared. This data can be retained with the following PLC Setup set-
tings: IOM Hold Bit Status at Startup and Forced Status Hold Bit Status at
Startup.
Type
Name
1
Extension
Description
Explanation
Data file
BACKUP
.IOM
DM Area words allo-
cated to Special I/O
Units, CPU Bus
Units, and Inner
Boards (CS Series
only)
• Contains DM data from D20000 to D32767.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
BACKUPIO
.IOR
I/O memory data
areas
• Contains all of the data in the CIO, WR, HR, and
AR data areas as well as timer/counter Comple-
tion Flags and PVs.
2
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
BACKUPDM
.IOM
General-purpose DM
Area
• Contains DM data from D00000 to D19999.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
BACKUPE
@
.IOM
General-purpose EM
Area
Contains all of the EM data for EM bank
@
with
addresses ranging from E
@
_00000 to E
@
_32767.
(The maximum bank number depends upon the
model of CPU Unit being used.)
This file must exist on the Memory Card when read-
ing data from the Memory Card during backup.
• When data is backed up to the Memory Card, all
of the data in each EM bank is automatically writ-
ten to a separate file.
Program file
BACKUP
.OBJ
Entire user program
• Contains all cyclic and interrupt task programs as
well as task data for one CPU Unit.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
Parameter file
.STD
PLC Setup, regis-
tered I/O table, rout-
ing tables, CPU Bus
Unit settings
3
, etc.
• Contains all initial settings for one CPU Unit.
• The user does not have to distinguish parameter
data in the file by type.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
Unit/Board
backup files
(CS1-H, CJ1-
H, or CJ1M
CPU Units
only)
BACKUP
@@
(where
@@
is
the unit
address of
the
Unit/Board
being backed
up)
.PRM
Data for specific Unit
or Board
• Control backup data from one Unit or Board.
Refer to 5-2-6 Simple Backup Function for
details.
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...