![NF EC1000SA Instruction Manual Download Page 156](http://html1.mh-extra.com/html/nf/ec1000sa/ec1000sa_instruction-manual_1684880156.webp)
5.4
MEASURE Screen
EC1000SA
5-26
5.4.6 Output harmonic current measurement
Output harmonic current measurement is enabled only in the AC-INT mode and when the frequency
setting is 50 Hz or 60 Hz.
When HC1, HC2, HC3, or HC4 is selected under “MEASURE” in the MISC menu, the harmonic
measurement window is displayed.
At that time, measurements other than output harmonic measurement are not performed. This
measurement does not conform to the IEC or other standards.
See
“4.3 Measurement of Harmonic Current”
.
•
Measurement range:
To 40th harmonic of fundamental wave
•
Full scale:
15.00 Arms and 500.0%
•
Display resolution:
0.01 Arms and 0.1%
•
Measurement accuracy:
at RMS value current up to 10th
±
(1% of rdg + 0.08 Arms)
at RMS value current from 11th up to 20th
±
(2% of rdg + 0.08 Arms)
at RMS value current from 21st up to 40th
±
(5% of rdg + 0.08 Arms)
(All in the case of reference value, 23
±
5°C)
Note
: This measurement does not conform to the IEC or other standards.
5.4.7 External synchronization frequency measurement
The frequency measured value is displayed only in the external synchronization mode (AC-SYNC or
AC+DC-SYNC).
See “4.7 Synchronize the Output with External Signal”
.
•
Measurement range:
38.0 Hz to 525.0 Hz
•
Display resolution:
0.1 Hz
•
Measurement accuracy:
±
0.2 Hz (at 23
±
5°C)
Summary of Contents for EC1000SA
Page 1: ...NF Corporation PROGRAMMABLE AC DC POWER SOURCE EC1000SA Instruction Manual nbn Austria GmbH...
Page 2: ...DA00036667 003 PROGRAMMABLE AC DC POWER SOURCE EC1000SA Instruction Manual...
Page 236: ...6 9 Notes on Remote Control EC1000SA 6 58...
Page 260: ...8 5 Backup Battery EC1000SA 8 8...
Page 280: ...9 17 External Dimensions and Weight EC1000SA 9 20...