14 - 6
14. CONNECTION TO SIEMENS PLC
14.2 Serial Connection
14.2.4
GOT Side Settings
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: SIEMENS
• Controller Type: Set either of the following.
S7-300/400
S7-200
• I/F: Interface to be used
• Driver: Set either of the following.
When connecting to SIEMENS S7-300/400:
SIEMENS S7-300/400
When connecting to SIEMENS S7-200:
SIEMENS S7-200
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
(1) SIEMENS S7-300/400
*1
Set the address without overlapping the address of other
units.
*2
The GOT automatically sets the values of Transmission
Speed, Adapter Address, and Host Address to the HMI
Adapter.
2.
3.
4.
Click!
Item
Description
Range
Transmission
Speed
*2
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 38400bps)
9600bps,
19200bps,
38400bps
Data Bit
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bit)
8bit (fixed)
Stop Bit
Specify the stop bit length for
communications.
(Default: 1bit)
1bit (fixed)
Parity
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Odd)
Odd (fixed)
Adapter
Address
*1*2
Specify the adapter address (station
No. of the adapter to which the GOT
is connected) in the connected
network.
(Default: 1)
1 to 31
Host Address
*1*2
Specify the host address (station No.
of the PLC that the GOT will monitor)
in the connected network.
(Default: 2)
1 to 31
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......