9 - 48
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
9.5.14
Connecting to SA100/SA200
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
9.5.15
Connecting to X-TIO Module
(1) Communication settings
Make the communication settings of the temperature
controller.
*1
Adjust the settings with GOT settings.
*2
When the setting value is set to 0, a communication is not
made.
(2) Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol.
(3) Module address settings
Set the unit address using the rotary switch (address
setting switch).
Item
Setting range
Communication speed
*1
9600bps, 19200bps
Data bit configuration
*1
(Data bit, Parity bit, Stop bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address
*2
(Slave address)
1 to 99
*4
Interval time
*3
0 to 250 (ms)
Item
Setting range
Communication speed
*1
9600bps, 19200bps, 38400bps
Communication protocol
MODBUS
Data bit configuration
Data bit: 8bit, Parity: None
Data bit: 8bit, Parity: Even
Data bit: 8bit, Parity: Odd
Stop bit: 1bit (fixed)
Module address
*2
1 to 99
Internal data bus
terminating resistor
When combining the module, turn ON the
internal data bus terminating resistor at both
ends of the module.
Data interval extension
time
0 to 99ms
Setting item
Set value
Switch position
1
2
3
4
5
6
7
8
Communicati
on speed
9600bps
ON OFF
19200bps
OFF ON
38400bps
ON
ON
Data bit
configuration
Data bit: 8bit,
Parity: None
ON OFF OFF
Data bit: 8bit,
Parity: Even
ON OFF ON
Data bit: 8bit,
Parity: Odd
ON
ON
ON
Communicati
on protocol
MODBUS
ON
Internal data
bus
termination
resistor
setting
OFF
OFF
ON
ON
Data interval
extension
time
0 to 99ms
ON OFF ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
OFF
Dip switch
5
4
3
2
1
0
9
8
7
6
5
5
4
3
2
1
0
9
8
7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
5
4
3
2
1
0
9
8
7
6
5
5
4
3
2
1
0
9
8
7
6
5
Upper digit setting
(Set value x10)
Lower digit setting
(Set value x1)
Rotary switch
(Address setting switch)
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......