11. CONNECTION TO GE PLC
11.5 PLC Side Setting
11 - 13
CONNECTION T
O
GE PLC
11
11.5 PLC Side Setting
POINT
POINT
POINT
GE PLC
For details of GE PLCs, refer to the following manuals.
GE PLC user's Manual
11.5.1
Connecting to Series 90-30
Communication settings
Make the communication settings using the
engineering tool.
When making the settings, set [Configuration Mode] on
the [Setting] tab of the engineering tool to "SNP only".
*1
Set to SNP.
*2
Set to Slave.
*3
Set to Long.
*4
Set to 0.
*5
Set within the range of 00 to 31.
When specifying the station No. from 0 to 9, add "0" before
the number and set it as 00 to 09.
*6
Set to 0.(only when connecting to Port2)
11.5.2
Connecting to VersaMaxMicro
Communication settings
Make the communication settings using the
engineering tool.
*1
Set to the SNP protocol.
*2
Set to Slave.
*3
Set to Long.
*4
Set to 0.
*5
Set within the range of 00 to 31.
When specifying the station No. from 0 to 9, add "0" before
the number and set it as 00 to 09.
Model name
Refer to
PLC CPU
Series 90-30
VersaMaxMicro
Communication
Modules
IC693CMM311
IC697CMM711
Setting item
PLC side setting
Port Mode
*1
SNP
Port Type
*2
Slave
Data Rate
9600bps, 19200bps
Flow Control
NONE
Parity
EVEN, ODD, NONE
Stop Bits
1bit, 2bits
Timeout
*3
Long
Turn Around Delay
*4
0
SNP ID
*5
00 to 31
Converter Power Consumption
*6
0
Setting item
PLC side setting
Data Rate
9600bps, 19200bps,
38400bps
Bits / Character
7bits, 8bits
Parity
EVEN, ODD, NONE
Stop Bits
1bit, 2bits
Port Mode
*1
SNP
Port Type
*2
Slave
Flow Control
NONE
Timeout
*3
Long
Turn Around Delay
*4
0
SNP ID
*5
00 to 31
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......