8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.4 GOT Side Settings
8 - 27
8
CON
N
ECTION
T
O
YOKOGA
W
A
TEMPERA
T
URE C
O
NTROLLER
8.4
GOT Side Settings
8.4.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YOKOGAWA
• Controller type: YOKOGAWA GREEN/UT100/
UT2000/UTAdvanced
• I/F: Interface to be used
• Driver: YOKOGAWA GREEN/UT100/UT2000/
UTAdvanced
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
8.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
8.4.2
Communication detail settings
2.
3.
4.
Click!
Item
Description
Range
Transmission
Speed
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
Set this item when change the data
length used for communication with the
connected equipment.
(Default: 8bits)
7bits/8bits
Stop Bit
Specify the stop bit length for
communications.
(Default: 1bit)
1bit/2bits
Parity
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: Even)
None
Even
Odd
Sum Check
Set whether or not to perform a sum
check during communication.
(Default: No)
Done, None
Retry
Set the number of retries to be performed
when a communication error occurs.
(Default: 0time)
0 to 5times
Timeout
Time
Set the time period for a communication
to time out.
(Default: 3sec)
1 to 30sec
Host Address
Specify the host address (station No. of
the GOT to which the temperature
controller is connected) in the connected
network.
(Default: 1)
1 to 99
Delay Time
Set this item to adjust the transmission
timing of the communication request from
the GOT.
(Default: 5ms)
0 to 300ms
Format
Select the communication format.
(Default: 1)
Format 1:
Accessible to GREEN/UT100/UT2000/
UTAdvanced Series
Format 2:
Accessible to GREEN/UT2000/
UTAdvanced Series, Not accessible to
UT100 Series.
1/2
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......