8 - 22
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.3 Connection Diagram
(16) RS-485 connection diagram 16)
*1
Pin No. of temperature controller differs depending on the model. Refer to the following table.
• For the product condition of UTAdvanced series, refer to the following table.
*2
Terminating resistor should be provided for a temperature controller which will be a terminal.
*3
Turn on the terminating switch on the RS232C/RS485 converter at the end.
*4
Connect FG grounding to the appropriate part of a cable shield line.
RDA(-)
RDB(+)
SDA(-)
SDB(+)
SG
3
4
1
2
5
6
RDA(-)
RDB(+)
SDA(-)
SDB(+)
SG
RDA(-)
RDB(+)
SDA(-)
SDB(+)
SG
GND
*4
*4
Temperature controller
*1
Temperature controller
*1
RS232C/RS485
interface converter
*3
Terminating resistor (220Ω 1/4W)
*2
Signal name
Model of temperature controller
UTAdvanced Series
UT32A/UP35A/UM33A
UT35A/
UT55A (product condition A)/
UP55A (product condition A)
UT55A (product condition B)/
UP55A (product condition B)
Pin No.
Pin No.
Pin No.
SDB (+)
301
407
501
SDA (-)
302
408
502
RDB (+)
304
410
504
RDA (-)
305
411
505
SG
303
409
503
Model
Product
condition
Suffix code
Optional suffix code
Remark
Function
Open network
UT55A
A
-
1
-
Product with the open network port of RS-
485 communication (4-wire type/2-wire
type)
B
1 or 2
-
Without "/LP"
Product with two RS-485 communication
ports (4-wire type/2-wire type) and without
the power supply for 24VDC sensor
UP55A
A
Other than 3
1
-
Product without the additional contact
output points (DO) and with the open
network port of RS-485 communication (4-
wire type/2-wire type) (Standard code
model)
-
-
With "/CH3"
Product with the RS-485 communication
port (4-wire type/2-wire type) specified in
the E3 terminal area option (Detailed code
model)
B
2
-
-
Product with two RS-485 communication
ports (4-wire type/2-wire type) (Standard
code model)
-
-
With "/C4"
Product with the RS-485 communication
port (4-wire type/2-wire type) specified in
the E4 terminal area option (Detailed code
model)
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......