6. CONNECTION TO YASKAWA PLC
6.3 Ethernet Connection
6 - 17
6
CONNECTION T
O
Y
A
SK
A
W
A PLC
6.3
Ethernet Connection
6.3.1
System configuration for connecting to MP-920 or MP2200 or MP2300 or
MP2300S or CP-9200SH or CP-312 or CP-317
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
Product manufactured by YASKAWA Electric Corporation. For details of the product, contact YASKAWA Electric Corporation.
Communications
Module
MP920,MP2200,
MP2300,
CP-9200SH,CP-312,
CP-317
GOT
Connection cable
Ethernet(
YASKAWA
), Gateway
Communication driver
PLC
Connection cable
GOT
Number of connectable
equipment
Model name
Communication
module
*3
Cable model
*1
Maximum
segment
length
*2
Option device
Model
MP-920
218IF
• 100BASE-TX
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP)
of category 5 or higher
• 10BASE-T
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP)
of category 3 or higher
100m
- (Built into GOT)
When PLC (module):GOT is N:1
The following shows the number
of PLCs for 1 GOT
TCP: 128 or less
UDP: 128 or less
When PLC (module):GOT is 1:N
The following shows the number
of GOTs for 1 PLC (module)
TCP/UDP: 10 or less
MP2200
MP2300
MP2300S
218IF-01
218IF-02
CP-9200SH
CP-312
CP-218IF
CP-317
218TXB
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......