6 - 20
6. CONNECTION TO YASKAWA PLC
6.3 Ethernet Connection
6.3.4
PLC side setting (MP2000
series, MP920 series)
POINT
POINT
POINT
YASKAWA PLC
For details of YASKAWA PLCs, refer to the following
manuals.
YASKAWA PLC user's Manual
Parameter settings
Make the parameter settings with a peripheral tool.
(1) Settings for 218IF-01
*1
When MITSUBISHI PLC and YASKAWA PLC are used
together in the same network, do not set the same value for
the Station of MITSUBISHI PLC and the CNO (Connection
number) of YASKAWA PLC.
*2
Set the same the Node IP Address (Remote Station's IP
Address) and the Node Port (Remote Station's Port Number)
as the Local IP Address and the Local Port (Local Station's
Port Number) on the GOT side.
For the Local IP Address and the Local Port (Local Station's
Port Number) on the GOT side, refer to the following.
■
(2) Setting for the built-in MP2300S Ethernet and 218IF-
02
*1
Set the same the Node IP Address (Remote Station's IP
Address) and the Node Port (Remote Station's Port Number)
as the Local IP Address and the Local Port (Local Station's
Port Number) on the GOT side.
For the Local IP Address and the Local Port (Local Station's
Port Number) on the GOT side, refer to the following.
■
Item
Set value
Range
Parameter
setting
Local IP Address
[ ].[ ].[ ].[ ]
PLC side IP
address
Response Time
0
Not required for
communication
with GOT
Count of Retry
(Number of Retries)
0
Not required for
communication
with GOT
CNO
*1
(Connection Number)
1
1 to 20
Local Port (Local
Station's Port Number)
10500
256 to 65534
Node IP Address
(Remote Station's IP
Address)
*2
[ ].[ ].[ ].[ ]
IP address
of GOT
Node Port (Remote
Station's Port Number)
*2
[ ]
Port No.
of GOT
Connection Type
UDP
(recommended)
UDP/TCP
Protocol Type
Extended
MEMOBUS
Extended
MEMOBUS,
MEMOBUS,
MELSEC,
None,
MODBUS/TCP
Code
BIN
RTU, BIN, ACII
Node Name (Remote
Station's Name)
GOT1000
Name of GOT
Local Port:
TCP/IP
Setting
Subnet Mask
[ ].[ ].[ ].[ ]
PLC side
setting
Gateway IP Address
[ ].[ ].[ ].[ ]
System Port No.
(Diagnostic/
Engineering Port No.)
10000
TCP (Transmission
Control Protocol) Zero
Window Timer Value
3 sec
TCP Retry Time
500ms
TCP Close Time
60 sec
IP Assemble Time
30 sec
MAX. Packet Length
1500 bytes
Item
Set value
Range
Transmission
parameter
setting
IP Address
[ ].[ ].[ ].[ ]
PLC side IP
address
Subnet Mask
[ ].[ ].[ ].[ ]
PLC side setting
Gateway IP Address
[ ].[ ].[ ].[ ]
Device name
Arbitrary
Up to 16 one-byte
characters
Transmission
parameter
detailed setting
Engineering Port
256 to 65535
For a connection
with software
MPE720
Response Time
0
Not required for
communication
with GOT
Count of Retry
(Number of Retries)
0
Message
communication
of connection
parameter
setting
Connection Number
1
• Range of built-
in MP2300S
Ethernet: 1 to 4
• Range of
218IF-02: 1 to
20
Local Port
10500
256 to 65534
Node IP Address
*1
[ ].[ ].[ ].[ ]
IP address
of GOT
Node Port
*1
[ ]
Port No.
of GOT
Connection Type
UDP
(recommended)
TCP/UDP
Protocol Type
Extended
MEMOBUS
Extended
MEMOBUS,
MEMOBUS,
MELSEC,
None,
MODBUS/TCP
Code
BIN
RTU, BIN, ACII
Node Name
Arbitrary
Up to 32 one-byte
characters
(16 two-byte
characters)
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......