![Mitsubishi GOT2000Series Connection Manual Download Page 207](http://html1.mh-extra.com/html/mitsubishi/got2000series/got2000series_connection-manual_1809187207.webp)
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.6 Device Range that Can Be Set
8 - 33
8
CON
N
ECTION
T
O
YOKOGA
W
A
TEMPERA
T
URE C
O
NTROLLER
8.6
Device Range that Can Be Set
The device ranges of controller that can be used for GOT
are as follows.
Note that the device ranges in the following tables are the
maximum values that can be set in GT Designer3.
The device specifications of controllers may differ
depending on the models, even though belonging to the
same series.
Please make the setting according to the specifications of
the controller actually used.
When a non-existent device or a device number outside
the range is set, other objects with correct device settings
may not be monitored.
Setting item
*1
The following shows the relation between station numbers of
the temperature controller and the GOT data register.
*2
When there is no setting for the CPU No. in the
communication settings on the temperature controller side,
set the CPU No. on the GOT side to (1) (default).
8.6.1
YOKOGAWA GREEN/UT100/
UT2000/UTAdvanced
*1
Only 16-bit (1-word) designation is allowed.
*2
This is available only for UP750 and UP550.
Item
Description
Device
Set the device name, device number, and bit number.
The bit number can be set only when specifying the bit of
word device.
CPU
No.
*2
Set the CPU No. (1, 2) of the device to be monitored.
When device B is selected, the CPU No. is fixed to 1.
Information
Displays the device setting range which are selected in [Device].
Network
Set the monitor target of the set device.
All
Select this item when writing data to all the
temperature controllers connected.
When bit specification of word device is performed,
data are written to the temperature controller of the
station No. set for [Host Address] of the
communication detail settings.
Monitoring and writing with bit specification of word
device are performed only for the station No. set for
[Host Address].
(When writing the data in numerical input, the data is
written to the connected temperature controller other
than the ones specified by the word device during
input, and the temperature controller set for [Host
Address] is monitored during other than input
(displaying).)
Statio
n No.
Select this item when monitoring the temperature
controller of the specified station No.
After selecting, set the station No. in the following
range.
1 to 99
: To monitor the temperature controller
of the specified station No.
100 to 115
: To specify the station No. of the
temperature controller to be monitored
by the value of GOT data register
(GD).
*1
Statio
n No.
GOT data register (GD)
Setting range
100
GD10
1 to 99
(If setting a value
outside the range
above, a device
range error
occurs.)
101
GD11
:
:
114
GD24
115
GD25
Device name
Setting range
Device No.
representation
Bi
t de
vi
ce
Internal relay (I)
I0001 to I7072
Decimal
Word device bit
*1
Specified bit of the
following word devices
―
W
o
rd
d
e
vi
ce
Data register (D)
*1
D0001 to D9000
Decimal
File register (B)
*1*2
B0001 to B1600
Bit device word
Converting bit devices
into word
―
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......