Parameter overview
Parameter
6 - 16
Func-
tion
Parameter
Name
Incre-
ments
Initial
value
Setting
range
Description
Para-
meter
copy
Para-
meter
clear
All
Para-
meter
clear
Refer
to
page
Rel
a
ted
pa
ramet
e
rs
✔
: enabled
—: disabled
Parameter unit
language switchover
145
PU display language
selection
1
1
0
Japanese
✔
—
—
1
English
2
German
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
—
146
Parameter for manufacturer setting. Do not set.
Detection of output current (Y12 signal)
and Detection of zero
current (Y13 signal)
150
Output current detec-
tion level
0.1%
150%
0–200%
Set the output current detection
level. 100% is the rated inverter
current.
✔
✔
✔
151
Output current detec-
tion signal delay time
0.1s
0s
0–10s
Set the output current detection
period. Set the time from when the
output current has risen above the
setting until the output current
detection signal (Y12) is output.
✔
✔
✔
152
Zero current detection
level
0.1%
5%
0–200%
Set the zero current detection
level. Suppose that the rated
inverter current at the specified
overload capacity is 100%.
✔
✔
✔
153
Zero current detection
time
0.01s
0.5s
0–1s
Set this parameter to define the
period from when the output cur-
rent drops below the Pr. 152 value
until the zero current detection
signal (Y13) is output.
✔
✔
✔
166
Output current detec-
tion signal retention
time
0.1s
0.1s
0–10 s
Set the retention time when the
Y12 signal is ON.
✔
✔
✔
9999
The Y12 signal ON status is retai-
ned. The signal is turned off at the
next start.
167
Output current detec-
tion operation selection
1
0
0
Operation continues when the Y12
signal is ON
✔
✔
✔
1
The inverter is brought to trip
when the Y12 signal is ON.
(E.CDO)
—
156
157
Refer to Pr. 22
—
158
Refer to Pr. 52
—
160
Extended function
display selection
1
0
0
Displays simple mode and
extended parameters
✔
✔
✔
9999
Displays only the simple mode
parameters
Tab. 6-1:
Parameter overview (16)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......