Useful functions
Parameter
6 - 272
Life alarm display and signal output (Y90 signal, Pr. 255)
Whether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current
limit circuit has reached the life alarm output level or not can be checked by Pr. 255 "Life alarm
status display" and life alarm signal (Y90).
Read the setting of parameter 255.
When the life alarm output level is reached, the bits are set as follows.
I001262E
Fig. 6-139:
Read parameter 255
I001261E
Fig. 6-140:
Bits of parameter 255
Call up Pr. 255
Read the setting of Pr. 255
The bit image is displayed
in decimal.
Control circuit capacitor life
Main circuit capacitor life
Cooling fan life
Inrush current limit circuit life