Parameter
Special operation
FR-D700 SC EC
6 - 253
Set point input calibration
Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.
Enter in C2 (Pr. 902) the frequency which should be output by the inverter at the deviation
of 0% (e.g. 0Hz).
In C3 (Pr. 902), set the voltage value at 0%.
Apply the voltage of 100% set point (e.g. 5V) to across terminals 2-5.
Enter in Pr. 125 the frequency which should be output by the inverter at the deviation of
100% (e.g. 50Hz).
In C4 (Pr. 903), set the voltage value at 100%.
Process value input calibration
Apply the input current of 0% detector setting (e.g. 4mA) across terminals 4-5.
Make calibration of the process value bias (%) using C6 (Pr. 904).
Apply the input current of 100% detector setting (e.g. 20mA) across terminals 4-5.
Make calibration of the process value gain (%) using C7 (Pr. 905).
NOTE
The frequency set in C5 (Pr. 904) and Pr. 126 should be the same as set in C2 (Pr. 902) and
Pr. 125.
I000050C
Fig. 6-130:
Input calibration
%
100
0
0
5
(V)
%
100
0
0 4
20
(mA)
50
0
0
100
(%)
Set point setting
Process value
Manipulated variable
Deviation
Manipulated variable (Hz)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......