Parameter overview
Parameter
6 - 20
Available only for the three-phase power input model.
Func-
tion
Parameter
Name
Incre-
ments
Initial
value
Setting
range
Description
Para-
meter
copy
Para-
meter
clear
All
Para-
meter
clear
Refer
to
page
Rel
a
ted
pa
ramet
e
rs
✔
: enabled
—: disabled
Input/output phase failure
protection selection
251
Output phase failure
protection selection
1
1
0
Without output phase failure
protection
✔
✔
✔
1
With output phase failure
protection
872
Input phase failure
protection selection
1
1
0
Without input phase failure
protection
✔
✔
✔
1
With input phase failure
protection
Display of the life of the inverter parts
255
Life alarm status
display
1
0
(0–15)
Display whether the control circuit
capacitor, main circuit capacitor,
cooling fan, and each parts of the
inrush current limit circuit has
reached the life alarm output level
or not. (Reading only)
—
—
—
256
Inrush current limit
circuit life display
1%
100%
(0–100%)
Display the deterioration degree of
the inrush current limit circuit.
(Reading only)
—
—
—
257
Control circuit
capacitor life display
1%
100%
(0–100%)
Display the deterioration degree of
the control circuit capacitor.
(Reading only)
—
—
—
258
Main circuit capacitor
life display
1%
100%
(0–100%)
Display the deterioration degree of
the main circuit capacitor.
(Reading only)
The value measured by Pr. 259 is
displayed.
—
—
—
259
Main circuit capacitor
life measuring
1
0
0/1
(2/3/8/9)
Setting "1" and switching the
power supply off starts the meas-
urement of the main circuit capaci-
tor life. When the Pr. 259 value is
"3" after powering on again, the
measuring is completed. Displays
the deterioration degree in Pr. 258.
✔
✔
✔
—
260
Refer to Pr. 72
Operation at instan
taneous power failure
261
Power failure stop
selection
1
0
0
Coasting to stop
When under voltage or power fail-
ure occurs, the inverter output is
shut off.
✔
✔
✔
1
When under voltage or a power
failure occurs, the inverter can be
decelerated to a stop.
2
When under voltage or a power
failure occurs, the inverter can be
decelerated to a stop. If power is
restored during a power failure,
the inverter accelerates again.
—
267
Refer to Pr. 73
268
Refer to Pr. 52
269
Parameter for manufacturer setting: Do not set.
Tab. 6-1:
Parameter overview (20)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......