Parameter
Operation selection at power failure
FR-D700 SC EC
6 - 137
Power failure deceleration signal (Y46 signal)
The Y46 signal is on during deceleration at an instantaneous power failure or during a stop after
deceleration at an instantaneous power failure.
After a power failure stop, the inverter can not start even if power is restored the start command
is given. In this case, check the power failure deceleration signal (Y46 signal) (at occurrence of
input phase loss (E.ILF), etc.).
In case of a power failure, signal Y46 is connected through during the brake time or in standstill
after expiration of the brake time. For the Y46 signal, set "46" (forward operation) or "146" (re-
verse operation) to any of Pr. 190, Pr. 192 or Pr. 197 to assign the function.
NOTES
During a stop or trip, the power failure stop selection is not performed.
Signal Y46 is switched on in case of undervoltage, even if the brake is not applied to the
motor during a temporary power failure. For this reason, Signal Y46 is permanently output
during the switch-on routine. This is NOT an error.
Changing the terminal assignment using Pr. 190, Pr. 192 and Pr. 197 may affect the other
functions. Please make setting after confirming the function of each terminal.
b
CAUTION:
If power-failure deceleration operation is set, some loads may cause the inverter to
trip and the motor to coast. The motor will coast if enough regenerative energy is given
from the motor.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......