Parameter
Frequency setting by external terminals
FR-D700 SC EC
6 - 53
JOG operation from PU
Selects Jog operation mode from the operation panel and PU (FR-PU04/FR-PU07). Operation
is performed only while the start button is pressed.
Fig. 6-21:
Connection example for jog operation
performed from PU
I002028E
I001791E
Fig. 6-22:
JOG operation performed from PU
Power
supply
Motor
Inverter
Operation panel
Confirmation of the RUN indication and operation
mode indication.
The monitor mode must have been selected.
The inverter must be at a stop.
Press the PU/EXT key to choose the
PU JOG operation mode.
Press the RUN key.
The motor rotates while the key is pressed.
It rotates at 5Hz (initial value of Pr. 15).
Release the RUN key to stop the motor.
When changing the frequency of PU JOG operation:
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until Pr. 15 "JOG frequency"
appears.
Press the SET key to show the currently set value
(5Hz).
Turn the digital dial to set the value to "10.00"
(10.00Hz).
Press the SET key to set.
Perform the operations in steps
to
The motor rotates at 10Hz.
Hold down
Stop
Operation
Display
Release
The parameter number read previously
appears.
Flicker ... Parameter setting complete!
"PRM" indication is lit.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......