Maintenance and inspection
Inspection
FR-D700 SC EC
8 - 5
8.1.5
Checking the inverter and converter modules
Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
Prepare a tester. (Use 100
Ω
range.)
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W,
P/+ and N/
−
, and check for continuity.
At the time of discontinuity, the measured value is almost
앝
. When there is an instantaneous
continuity, due to the smoothing capacitor, the tester may not indicate
앝
. At the time of conti-
nuity, the measured value is several to several ten’s-of ohms depending on the module type, cir-
cuit tester type, etc. If all measured values are almost thesame, the modules are without fault.
T/L3, D3 and D6 are only for the three-phase power input specification models.
b
CAUTION:
Before measurement, check that the smoothing capacitor is discharged. The measu-
ring device can otherwise be destroyed
Fig. 8-1:
Module device numbers and terminals to be
checked
I002039E
Tester Polarity
Measured Value
Tester Polarity
Measured Value
Converter
module
D1
R/L1
P/+
Discontinuity
D4
R/L1
N/–
Continuity
P/+
R/L1
Continuity
N/–
R/L1
Discontinuity
D2
S/L2
P/+
Discontinuity
D5
S/L2
N/–
Continuity
P/+
S/L2
Continuity
N/–
S/L2
Discontinuity
D3
T/L3
P/+
Discontinuity
D6
T/L3
N/–
Continuity
P/+
T/L3
Continuity
N/–
T/L3
Discontinuity
Inverter
module
TR1
U
P/+
Discontinuity
TR4
U
N/–
Continuity
P/+
U
Continuity
N/–
U
Discontinuity
TR3
V
P/+
Discontinuity
TR6
V
N/–
Continuity
P/+
V
Continuity
N/–
V
Discontinuity
TR5
W
P/+
Discontinuity
TR2
W
N/–
Continuity
P/+
W
Continuity
N/–
W
Discontinuity
Tab. 8-3:
Continuity check of the modules
Converter module
Inverter module
N/–
P/+
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......