Function assignment of external terminals
Parameter
6 - 92
MRS signal logic inversion
When Pr. 17 is set to "2", the MRS signal (output stop) can be changed to the normally closed
(NC contact) input specification. When the MRS signal turns on (opens), the inverter shuts off
the output.
Assign a different action for each MRS signal input from communication and external
terminal (Pr. 17 = 4)
When Pr. 17 is set to "4", the MRS signal from external terminal (output stop) can be changed
to the normally closed (NC contact) input, and the MRS signal from communication can be
changed to the normally open (NO contact) input. This function is useful to perform operation by
communication with MRS signal from external terminal remained on.
Fig. 6-44:
Connection of the MRS terminal in source
logic
I000011C
External MRS
Communication
MRS
Pr. 17
0
2
4
OFF
OFF
Operation enabled
Output shutoff
Output shutoff
OFF
ON
Output shutoff
Output shutoff
Output shutoff
ON
OFF
Output shutoff
Output shutoff
Operation enabled
ON
ON
Output shutoff
Operation enabled
Output shutoff
Tab. 6-12:
Activating the output shutoff by external signal or communication
NOTES
When using an external terminal to input the MRS signal, the MRS signal shuts off the out-
put in any of the operation modes.
Changing the terminal assignment using Pr. 178 to Pr. 182 may affect the other functions.
Make setting after confirming the function of each terminal.
Pr. 17 = 0
PC
MRS
PC
MRS
Pr. 17 = 2
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......