Parameter
Monitor display and monitor output signals
FR-D700 SC EC
6 - 113
Frequency setting to output terminal status on the PU main monitor are selected by "other
monitor selection" of the parameter unit (FR-PU04/FR-PU07).
The cumulative energization time and actual operation time are accumulated from 0 to 65535
hours, then cleared, and accumulated again from 0.When the operation panel is used, the
time is displayed up to 65.53 (65530h) on the assumption that 1h = 0.001, and thereafter,
it is added up from 0.
Actual operation time is not accumulated when the cumulative operation time is less than
1h until turning off of the power supply.
When using the parameter unit (FR-PU04/FR-PU07), "kW" is displayed.
Since the panel display of the operation panel is 4 digits in length, the monitor value of more
than "9999" is displayed "----".
Larger thermal value between the motor thermal and transistor thermal is displayed.
A value other than 0% is displayed if the ambient temperature (heatsink temperature) is high
even when the inverter is at a stop.
Types of Monitor
Unit
Pr. 52
Pr. 158 (AM)
Terminal AM
Full Scale Value
Description
Opera-
tion
panel
PU
Main
Monitor
Actual operation
time
1h
23
—
—
Adds up and displays the
inverter operation time.
You can check the numbers of
the monitor value exceeded
65535h with Pr. 564. Can be
cleared by Pr. 171. (Refer to
page 6-116.)
Motor load factor
0.1%
24
24
200%
Displays the output current
value on the assumption that
the inverter rated current value
is 100%.
Monitor value = output power
monitor value/rated inverter cur-
rent
×
100 [%]
Cumulative power
0.01kWh
25
—
—
Adds up and displays the power
amount based on the output
power monitor.
Can be cleared by Pr. 170.
(Refer to page 6-116.)
PID set point
0.1%
52
52
100%
Display the set point, measured
value and deviation during PID
control. (Refer to page 6-242 for
details.)
PID measured value
0.1%
53
53
100%
PID deviation value
0.1%
54
—
—
Inverter I/O terminal
monitor
—
55
—
—
—
Displays the ON/OFF status of
the inverter input terminal and
output terminal on the PU (Refer
to page 6-116 for display on the
operation panel.)
Motor thermal load factor
0.1%
61
61
Thermal relay opera-
tion level (100%)
Motor thermal heat cumulative
value is displayed.
(Motor overload trip (E.THM) at
100%)
Inverter thermal load
factor
0.1%
62
62
Thermal relay opera-
tion level (100%)
Transistor thermal heat cumula-
tive value is displayed.
(Inverter overload trip (E.THT) at
100%)
PTC thermistor
resistance
0.01k
Ω
64
—
—
Displays the PTC thermistor
resistance at terminal 2 when
PTC thermistor protection is
active. (0.10k
Ω
to 31.5k
Ω
) (refer
Tab. 6-19:
Monitor description list (2)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......