Adjust the output torque (current) of the motor
Parameter
6 - 28
NOTES
The RT signal acts as the second function selection signal and makes the other second
functions valid. (Refer to section 6.9.3.)
The amount of current flows in the motor may become large according to the conditions such
as the motor characteristics, load, acceleration/deceleration time, wiring length, etc., resul-
ting in an overcurrent trip (OL (overcurrent alarm) then E.OC1 (overcurrent trip during acce-
leration), overload trip (E.THM (motor overload trip), or E.THT (inverter overload trip). (When
a fault occurs, release the start command, and decrease the Pr. 0 setting 1% by 1% to
reset.)
The Pr. 0, Pr. 46 settings are valid only when V/f control is selected.
When using the inverter dedicated motor (constant torque motor) with the FR-D740-120SC
and 160SC, set torque boost value to 2%. When Pr. 0 = 3% (initial value), if Pr. 71 value is
changed to the setting for use with a constant-torque motor, the Pr. 0 setting changes to 2%.
Changing the terminal assignment using Pr. 178 to Pr. 182 "Input terminal function selec-
tion" may affect the other functions. Please make setting after confirming the function of
each terminal.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......