Parameter
Function assignment of external terminals
FR-D700 SC EC
6 - 99
Setting
Terminal
Function
Operation
Related
Parameters
Refer to
Page
Source
Logic
Sink
Logic
8
108
THP
Electronic thermal O/L relay
pre-alarm
Output when the electronic
thermal relay function cumu-
lative value reaches 85%.
(Electronic thermal relay
function protection (E.THT/
E.THM) activates, when the
value reached 100%.)
Pr. 9, Pr. 51
11
111
RY
Inverter operation ready
Output when the inverter can
be started by switching the
start signal on or while it is
running.
—
12
112
Y12
Output current detection
Output when the output cur-
rent is higher than the Pr. 150
setting for longer than the
time set in Pr. 151.
Pr. 150, Pr. 151
13
113
Y13
Zero current detection
Output when the output
power is lower than the
Pr. 152 setting for longer than
the time set in Pr. 153.
Pr. 152, Pr. 153
14
114
FDN
PID lower limit
Output when the feedback
value falls below the lower
limit of PID control.
Pr. 127–Pr. 134,
Pr. 575–Pr. 577
15
115
FUP
PID upper limit
Output when the feedback
value rises above the upper
limit of PID control.
16
116
RL
PID forward/reverse rotation
output
Output when forward rotation
is performed in PID control.
25
125
FAN
Fan fault output
Output at the time of a fan
fault.
Pr. 244
26
126
FIN
Heatsink overheat prealarm
Output when the heatsink
temperature reaches about
85% of the heatsink overheat
protection providing tempera-
ture.
—
46
146
Y46
During deceleration at occur-
rence of power failure (retained
until release)
Output when the power fail-
ure-time deceleration function
is executed.
Pr. 261
47
147
PID
During PID control activated
Output during PID control.
Pr. 127–Pr. 134,
Pr. 575–Pr. 577
64
164
Y64
During retry
Output during retry
processing.
Pr. 65–Pr. 69
70
170
SLEEP
PID output interruption
Output when the PID output
interruption function is exe-
cuted.
Pr. 127–Pr. 134,
Pr. 575–Pr. 577
80
180
SAFE
Safety monitor output
Output while safety stop func-
tion is activated.
—
81
181
SAFE2
Safety monitor output 2
Output while safety circuit
fault (E.SAF) is not activated.
—
Tab. 6-15:
Output terminal function assignment (2)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......