Parameter
Energy saving operation
FR-D700 SC EC
6 - 143
6.13 Energy
saving
operation
6.13.1
Optimum excitation control (Pr. 60)
Without a fine parameter setting, the inverter automatically performs energy saving operation.
This inverter is optimum for fan and pump applications.
The above parameter can be set when Pr. 160 = 0.
When parameter is read using the FR-PU04, a parameter name different from an actual
parameter is displayed.
When "9" is set in Pr. 60, the inverter operates in the optimum excitation control mode.
The optimum excitation control mode is a control system which controls excitation current to im-
prove the motor efficiency to maximum and determines output voltage as an energy saving
method.
Purpose
Parameters that must be set
Refer to
Section
Energy saving operation
Energy saving operation and optimum
excitation control
Pr. 60
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
60
Energy saving control
selection
0
0
Normal operation mode
57
General-purpose
magnetic flux vec-
tor control
Restart coasting
time
9
Optimum excitation control mode
NOTES
When the motor capacity is too small as compared to the inverter capacity or two or more
motors are connected to the inverter, the energy saving effect is not expected.
When the optimum excitation control mode is selected, deceleration time may be longer than
the setting value. Since overvoltage alarm tends to occur as compared to the constant
torque load characteristics, set a longer deceleration time.
Optimum excitation control functions only under V/f control. Optimum excitation control does
not function under general-purpose magnetic flux vector control.
Optimum excitation control will not be performed during an automatic restart after instanta-
neous power failure.
Since output voltage is controlled by optimum excitation control, output current may slightly
increase.
V/F
V/F
V/F
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......