Parameter
Adjust the output torque (current) of the motor
FR-D700 SC EC
6 - 29
6.2.2
General-purpose magnetic flux vector control (Pr. 9, Pr. 71, Pr. 80)
Large starting torque and low speed torque are available with general-purpose magnetic flux
vector control.
What is general-purpose magnetic flux vector control?
The low speed torque can be improved by providing voltage compensation to flow a motor cur-
rent which meets the load torque. With setting slip compensation (Pr. 245 to Pr. 247), output fre-
quency compensation (slip compensation) is made so that the actual motor speed goes closer
to a speed command value. Effective when load fluctuates drastically, etc.
General-purpose magnetic flux vector control of the FR-D700 SC series is the same function as
the FR-E500 series.
The above parameters can be set when Pr. 160 = 0.
Refer to appendix A for the rated inverter output current.
Control mode
●
V/f control and general-purpose magnetic flux vector control are available with the
FR-D700 SC inverters.
●
V/f control is for controlling frequency and voltage so that the ratio of frequency (f) to voltage
(V) is constant when changing frequency.
●
General-purpose magnetic flux vector control divides the inverter output current into an
excitation current and a torque current by vector calculation, and makes voltage compen-
sation to flow a motor current which meets the load torque.
(General-purpose magnetic flux vector control is the same function as the FR-E500 series.)
Pr.
No.
Name
Initial
Value
Setting Range
Description
Parameters referred to
Refer to
Section
9
Electronic ther-
mal O/L relay
Rated
inverter
output
current
0–500A
Set the rated motor current.
3
19
71
77
178–182
Base frequency
Base frequency
voltage
Applied motor
Parameter write
selection
I
nput terminal
function
selection
71
Applied motor
0
0/1/3/13/23/40/
43/50/53
By selecting a standard motor or constant
torque motor, thermal characteristic and
motor constants of each motor are set.
80
Motor capacity
9999
0.1–7.5kW
Applied motor capacity.
9999
V/f control
NOTES
If the following conditions are not satisfied, select V/F control since malfunction such as
insufficient torque and uneven rotation may occur.
●
The motor capacity should be equal to or one rank lower than the inverter capacity. (The
capacity should be 0.1kW or more.)
●
Motor to be used is any of Mitsubishi standard motor
(SF-JR, SF-HR 0.2kW or more) or
Mitsubishi constant-torque motor (SF-JRCA four-pole, SF-HRCA 0.2kW to 7.5kW). When
using a motor other than the above (other manufacturer's motor), perform offline auto
tuning without fail.
Single-motor operation (one motor run by one inverter) should be performed.
The wiring length from inverter to motor should be within 30m. Otherwise, the drive beha-
viour may be impaired or the offline auto tuning may be cancelled and an appropriate alarm
issued. Perform offline auto tuning in the state where wiring work is performed when the wir-
ing length exceeds 30m.
Permissible wiring length between inverter and motor differs according to the inverter capac-
ity and setting value of Pr. 72 "PWM frequency selection" (carrier frequency). (Refer to page
3-11).
GP MFVC
GP MFVC
GP MFVC
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......