Set V/f pattern
Parameter
6 - 44
6.4 Set
V/f
pattern
6.4.1
Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47)
Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
The above parameter can be set when Pr. 160 = 0.
Setting of base frequency (Pr. 3)
When operating a standard motor, generally set the rated frequency of the motor to Pr. 3 "Base
frequency".
When running the motor using commercial power supply-inverter switch-over operation, set
Pr. 3 to the same value as the power supply frequency.
If the frequency given on the motor rating plate is "60Hz" only, always set to "60Hz". It may result
in an inverter trip due to overload. Caution must be taken especially when Pr. 14 "Load pattern
selection" = "1" (variable torque load)
Purpose
Parameters that must be set
Refer to
Section
Set motor ratings
Base frequency, Base frequency voltage
Pr. 3, Pr. 19,
Pr. 47
Select a V/f pattern according to
applications
Load pattern selection
Pr. 14
Pr.
No.
Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
3
Base frequency
50Hz
0–400Hz
Set the frequency when the motor
rated torque is generated. (50Hz/
60Hz)
14
29
83
84
178–182
Load pattern
selection
Acceleration/decel-
eration pattern
selection
Motor rated
voltage
Rated motor fre-
quency
Input terminal
function selection
General-purpose
magnetic flux vec-
tor control
19
Base frequency
voltage
8888
0–1000V
Set the rated motor voltage.
8888
95% of power supply voltage
9999
Same as power supply voltage
47
Second V/f
(base frequency)
9999
0–400Hz
Set the base frequency when the RT
signal is on.
9999
Second V/f invalid
I000003aC
Fig. 6-11:
Output voltage related to the output frequency
V/F
V/F
V/F
50 60
120
[Hz]
100
[%]
Base frequency setting range
Setting r
a
nge Pr
. 19
Output v
o
ltage
related to the
po
w
e
r supply v
o
ltage
Pr. 3 = 50Hz, Pr. 19 = 9999
Pr. 3 = 60Hz, Pr. 19 = 220V
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......