Misoperation prevention and parameter setting restriction
Parameter
6 - 168
6.16.4
Extended parameter display (Pr. 160)
Parameter 160 allows access to certain parameters via the control panel and the parameter unit
The above parameter allows its setting to be changed during operation in any operation mode
even if "0" is set in Pr. 77.
Display of simple mode parameters and extended parameters (Pr. 160)
When Pr. 160 = "9999", only the simple mode parameters can be displayed on the operation
panel and parameter unit (FR-PU04/FR-PU07). (Refer to the parameter list Tab. 6-1 for the
simple mode parameters.)
Setting "0" (initial value) to Pr. 160 enables the display of the simple mode parameters and
extended parameters.
Pr.
No.
Name
Initial
Setting
Setting
Range
Description
Parameters referred to
Refer to
Section
160
Extended function display
selection
0
9999
Displays only the simple mode parame-
ters.
15
16
551
Jog frequency
Jog acceleration/
deceleration time
PU mode operation
command source
selection
0
Displays simple mode and extended
parameters.
NOTES
When RS485 communication is used to read the parameters, all parameters can be read -
regardless of Pr. 160 setting - by setting a value
≠
"2" in Pr. 551 "PU mode operation com-
mand source selection".
Pr. 15 "Jog frequency", Pr. 16 "Jog acceleration/deceleration time", and Pr. 991 "PU contrast
adjustment" are displayed as simple mode parameter when the parameter unit (FR-PU04/
FR-PU07) is fitted.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......