Edit a "Channel value range status" channel type
ON when outside range
The related "
" will be turned ON when the input channel value is greater than the
"
Upper limit
" or less than the "
Lower limit
". The related "
" will be turned OFF if the
input channel value is greater than the "
Lower limit
" plus the "
Hysteresis value
" or less than the "
Upper
limit
" minus the "
Hysteresis value
".
OFF when inside range
The related "
" will be turned ON when the input channel value is less than the "
Upper
limit
" and greater than the "
Lower limit
". The related "
" will be turned OFF if the
input channel value is greater than the "
Upper limit
" plus the "
Hysteresis value
" or less than the "
Lower
limit
" minus the "
Hysteresis value
".
In the example above, the "Binary status output" will be turned ON, when the "Source channel named -
Depth" has a value of between 1.0 and 0.5 metres, and OFF if the "Source channel named - Depth" has a
value of greater than 1.1 metres or less than 0.4 metres.