47DAC OPERATING MANUAL EM-9518-B Rev.4
1.7.9 WIRING BCD OUTPUT
BCD data in 6 digits and 5 alarm contacts including the P status are output.
SIGNAL ID
ITEM
RATING
Input
REQ, MIN_REQ, MAX_REQ, HOLD, RESET
Input signals
Dry contact or NPN open collector
Input current
≤ 3 mA
Sensing
6 V
Contact detecting
≤ 1.5 V at ON; ≥ 3 V at OFF
Output
DATA (Do11 to Do68), POL, OVF, DAV, RUN
Output signals
NPN open collector
Max. load voltage
24 V DC
Max. load current
10 mA
Saturation voltage
≤ 0.3 V
Leakage current
≤ 500 μA
HH, H, P, L, LL
Alarm output signals
NPN open collector
Max. load voltage
24 V DC
Max. load current
50 mA
Saturation voltage
≤ 1.1 V
Leakage current
≤ 500 μA
IMPORTANT
• Prepare the HDR40 and CNT separately for the BCD output.
• Refer to CONNECTOR PIN ASSIGNMENT to prepare a cable by yourselves.
• The connector model No. is HDR-EC50LFDT1-SLE+ (Honda Tsushin Kogyo Co., Ltd.).
• Be sure to confirm the polarity in wiring.
• Make sure that the saturation voltage (residual voltage) of an input device meets the detecting levels of the unit. Other-
wise the unit may not operate correctly.
• Connect load within the specifications.