47DAC OPERATING MANUAL EM-9518-B Rev.4
■
EVENT TRIGGER INPUT AND ALARM OUTPUT (PHOTO MOSFET RELAY)
• APPLICABLE WIRE SIZE
Solid: 0.5 to 1.25 mm
2
(max. 1.3 dia.)
Stranded: 0.5 to 1.25 mm
2
(max. 1.3 dia.)
IMPORTANT
• Tinning wire ends may cause contact failure and therefore is not recommended.
• Expose wire conductors by 7 to 8 mm (0.28 to 0.31”).
• RECOMMENDED FERRULE
The following Phoenix Contact terminals are recommended.
• For single-wire
• For twin-wire
CROSS-SECTION AREA
MODEL
CROSS-SECTION AREA
MODEL
0.5 to 0.75 mm
2
AI 0,75-8 GY
0.5 to 0.75 mm
2
AI-TWIN 2X 0,75-8 GY
0.75 to 1.0 mm
2
AI 1,0-8 RD
0.75 to 1.0 mm
2
AI-TWIN 2X 1,0-8 RD
1.0 to 1.5 mm
2
AI 1,5-8 BK
1.0 to 1.5 mm
2
AI-TWIN 2X 1,5-8 BK
8mm
8mm
Torque: 0.51 N∙m
Recommended manufacturer: Phoenix Contact GmbH & Co., KG
7 to 8 mm