47DAC OPERATING MANUAL EM-9518-B Rev.4
4
Apply 5% input and press Up button to register the value.
• The teach calibration (Zero) is registered.
• ‘Tch’ indicator turns on in green.
IMPORTANT
Confirm that the input signal is stable before pressing Up button.
5
Press Alarm/
↓
button twice to go to the input scaling value
Span setting.
• The input scaling value Span is indicated.
• The SD indicates ‘IN-B’.
• ‘Zro’ indicator turns off. ‘Spn’ and ‘Tch’ indicators turn on.
NOTE
Skip to Step 8 when the teach calibration (Span) is not necessary.
6
Press Up button to go to the teach calibration (Span) setting.
• The present input is indicated.
• ‘Tch’ indicator starts blinking in red.
NOTE
The decimal point position depends on the decimal point position setting. Disregard the decimal point to calibrate.
7
Apply 100% input and press Up button to register the value.
• The teach calibration (Span) is registered.
• ‘Tch’ indicator turns on in green.
IMPORTANT
Confirm that the input signal is stable before pressing Up button.
8
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.
Blinking