200
47DAC OPERATING MANUAL EM-9518-B Rev.4
25.1 CONFIGURATION OF ALARM SETPOINTS
25.1.1 OPERATING PROCEDURE
NOTE
• Procedures to change the LL alarm setpoint are
described here. To set other setpoints, the procedures
are same. Indicate a setpoint to change.
• The following figures are display examples. The dis-
plays depend on the specifications and settings.
1
Press Alarm/
↓
button to indicate the LL alarm setpoint on the
SD.
• The SD indicates the LL alarm setpoint.
• ‘LL’ indicator starts blinking.
2
Press Shift button to shift the SD into the setting standby
mode.
• The sixth digit starts blinking, to which you can apply changes.
3
Press Shift and Up buttons to set the LL alarm setpoint.
• Set within the range of -20000 to 100000.
IMPORTANT
Specify ‘------’ to disable the alarm output.
NOTE
Set the alarm setpoint with the decimal point position set in the decimal point position setting.
1,4
2,3
3
Blinking
Blinking
Blinking