169
47DAC OPERATING MANUAL EM-9518-B Rev.4
• TABLE 10: PEAK-TO-PEAK HOLD MODE
TIMING signal
While the TIMING signal is ON, the difference between
the MAX and MIN values with-in the period is measured
and stored, and is established at the rising edge of the
signal.
*
1 Scaling error
*
2 Measuring
TIMING
RESET
Scaling error range
P1
B2
B1
P2 – B2
0
P2
P1 – B1
*
2
*
2
*
1
Hold
Hold
Not measuring
TIMING within RESET: Invalid
Not measured if a scaling error occurs
while TIMING is ON
Not measuring
HOLD signal
While the HOLD signal is ON, the display reading is
held at the last measured value at the falling edge of the
signal, and the TIMING, S-TMR and ZERO signals are
invalid.
Scaling error
Stops data measuring.
RESET signal
Resets the measured data with the RESET signal ON
(no measurement). The TIMING signal is invalid.
DC output
Proportional to the display reading. For no measured
data, the value is 0%.
NOTE
• While the TIMING signal is ON, ‘TG‘ indicator turns on (right figure).
• The HOLD signal is ineffective when the RESET signal is ON.
• Except in the normal mode, the one-shot output is provided every measurement
timing regardless of the display refreshing rate.
• When the ZERO signal is ON, the Forced Zero and Tare Adjustment can be
executed or canceled regardless of the Forced Zero control lockout setting.
• The RESET signal does not affect the reference point measured by the Forced Zero and Tare Adjustment while they are
executed.
• The Forced Zero and Tare Adjustment can be executed or canceled with the ZERO signal while in MAX/MIN Value
Display mode or in confirming the alarm setpoints.
• The Forced Zero and Tare Adjustment cannot be executed or canceled with the ZERO signal while ‘S.ERR’ is indicated.
• The Forced Zero and Tare Adjustment cannot be executed or canceled for no measured data (RESET signal ON).
• The Forced Zero and Tare Adjustment cannot be executed or canceled with the ZERO signal while the HOLD signal is
ON.
• The MAX and MIN values can be reset with the RESET signal ON regardless of the MAX/MIN display control lockout
setting.
• The MAX and MIN values cannot be indicated with the front button control for no measured data.
• The MAX and MIN values are updated at the falling edge of the TIMING signal and indicated with the front button con-
trol in the sampling hold mode.
• The MAX and MIN values while the TIMING signal is ON are indicated with the front button control in the modes except
the normal and sampling hold modes.