238
47DAC OPERATING MANUAL EM-9518-B Rev.4
MODE
PARAMETER
SETTING RANGE
SUB DISPLAY /
INDICATOR
MAIN DISPLAY
DEFAULT
VALUE
DECIMAL
POINT
POSITION
UNIT
Alarm
setting
L alarm setpoint
-20000 – 100000
/
to
1:
*
1
User-defined
2:
L trip action
High trip, low trip
/
,
----
----
L deadband
(hysteresis)
0000 – 9999
/
to
----
User-defined
L ON delay time
000 – 999
/
to
----
100 ms
L OFF delay time
000 – 999
/
to
----
100 ms
L one-shot output
0000 – 9999
/
to
----
100 ms
L coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
H alarm setpoint
-20000 – 100000
/
to
1:
*
1
User-defined
2:
H trip action
High trip, low trip
/
,
----
----
H deadband
(hysteresis)
0000 – 9999
/
to
----
User-defined
H ON delay time
000 – 999
/
to
----
100 ms
H OFF delay time
000 – 999
/
to
----
100 ms
H one-shot output
0000 – 9999
/
to
----
100 ms
H coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
HH alarm setpoint
-20000 – 100000
/
to
1:
*
1
User-defined
2:
HH trip action
High trip, low trip
/
,
----
----
HH deadband
(hysteresis)
0000 – 9999
/
to
----
User-defined
HH ON delay time
000 – 999
/
to
----
100 ms
HH OFF delay time
000 – 999
/
to
----
100 ms
HH one-shot output
0000 – 9999
/
to
----
100 ms
HH coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
P ON delay time
000 – 999
/
to
----
100 ms
P OFF delay time
000 – 999
/
to
----
100 ms
P one-shot output
0000 – 9999
/
to
----
100 ms
P coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
Main display blinking
at alarm
No blinking, blinking in
1.0, 0.5, 0.3 sec. intervals
,
,
,
----
Second
Bank copy
No copying, copy current
bank value to all banks
,
----
----
*
1 Conforms to decimal point position setting.
NOTE 2: SUB DISPLAY/INDICATOR:
= ON,
= Blinking
NOTE 5: 1 and 2 in the columns of LL, L, H and HH alarm setpoints in Alarm Setting Mode show input codes.