40
47DAC OPERATING MANUAL EM-9518-B Rev.4
2.1.3 BASIC SETTING PROCEDURE
The following shows the procedure to set the input to 0 – 20 mA AC and the display to 0.00 – 600.00 A AC with the input
code ‘2’ as an example. Set values meeting signals of an equipment to use. Refer to 3. SETTING INPUT TYPE for details
of setting.
■
PARAMETER LIST FOR BASIC SETTING
Parameters used in the basic setting are as shown in the following table.
PARAMETER
SETTING VALUE
SUB DISPLAY
FUNCTION INDICATOR
SETTING
Input type
20MA
INTYPE
----
Measuring range: 0 – 20 mA
Input scaling value Zero
000.000
IN-A
Zro, Tch
0% input: 0.000 mA
Display scaling value Zero
000000
*
1
DISP-A
Zro
0% display: 0.00 A
Input scaling value Span
020.000
IN-B
Spn, Tch
100% input: 20.000 mA
Display scaling value Span
060000
*
1
DISP-B
Spn
100% display: 600.00 A
Decimal point position
000.00
D-POINT
----
2 decimal places (10
-2
)
*
1 The decimal point position depends on the decimal point position setting.
■
BASIC SETTING PROCEDURE
The basic setting procedure is as follows.
1
Confirm the wiring, turn on the power and move on to Scaling Setting Mode (measurement stopped).
• Hold down Scale/
↑
button for 3 seconds or more.
2
Set input type.
• Press Shift button to shift the display into the setting standby mode and Up button to select the input type.
3
Set scaling values in the order of input scaling value Zero, display scaling value Zero, input scaling value
Span and display scaling value Span.
• Press Alarm/
↓
or Scale/
↑
button to apply the new setting and go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode.
• Press Shift button to go to the next digit and Up button to change the blinking value.
4
Set decimal point position.
• Press Alarm/
↓
or Scale/
↑
button to apply the new setting and go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode and Up button to select the decimal point posi-
tion.
5
Return to Measuring Mode (measurement started).
• Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to apply the new setting and return to Measuring Mode.