245
47DAC OPERATING MANUAL EM-9518-B Rev.4
36.4.3 ALARM SETTING MODE
■
LOCKOUT ‘LV0’ (COMPLETELY UNLOCK ALARM SETTING MODE)
NOTE
The bank No. and bank copy are enabled with “enabled via the front button control” selected for the bank switching pa-
rameter.
for ≥ 3 sec.
for ≥ 1 sec.
Measurement
started
Measurement
stopped
Measuring Mode
or
Alarm Setting Mode
Bank No.
1 – 8
Alarm output pattern
Normal, Zone
LL alarm setpoint
-20000 to 100000
LL trip action
HIGHI (high trip)
LOW (low trip)
LL deadband
0000 – 9999
LL ON delay time
0.0 – 99.9 sec.
LL coil at alarm
EN (coil energized)
DN (coil de-energized)
LL OFF delay time
0.0 – 99.9 sec.
LL one-shot output
0.0 – 999.9 sec.
L alarm setpoint
-20000 to 100000
L trip action
HIGHI (high trip)
LOW (low trip)
L deadband
0000 – 9999
L ON delay time
0.0 – 99.9 sec.
L coil at alarm
EN (coil energized)
DN (coil de-energized)
L OFF delay time
0.0 – 99.9 sec.
L one-shot output
0.0 – 999.9 sec.
H alarm setpoint
-20000 to 100000
H trip action
HIGHI (high trip)
LOW (low trip)
H deadband
0000 – 9999
H ON delay time
0.0 – 99.9 sec.
H coil at alarm
EN (coil energized)
DN (coil de-energized)
H OFF delay time
0.0 – 99.9 sec.
H one-shot output
0.0 – 999.9 sec.
HH alarm setpoint
-20000 to 100000
HH trip action
HIGHI (high trip)
LOW (low trip)
HH deadband
0000 – 9999
HH ON delay time
0.0 – 99.9 sec.
HH coil at alarm
EN (coil energized)
DN (coil de-energized)
HH OFF delay time
0.0 – 99.9 sec.
HH one-shot output
0.0 – 999.9 sec.
P ON delay time
0.0 – 99.9 sec.
P coil at alarm
EN (coil energized)
DN (coil de-energized)
P OFF delay time
0.0 – 99.9 sec.
P one-shot output
000.0 – 999.9 sec.
Main display
blinking at alarm
No blinking,
blinking in 1.0, 0.5
or 0.3 sec. intervals
Bank copy
OFF (no copying)
ON (copy current bank value to all banks)