47DAC OPERATING MANUAL EM-9518-B Rev.4
■
MODE TRANSITION
■
TRANSITION FROM MEASURING MODE TO EACH MODE
To Scaling Setting Mode
Hold down Scale/
↑
button for 3 seconds or more.
To Alarm Setting Mode
Hold down Alarm/
↓
button for 3 seconds or more.
To Advanced Setting Mode
Hold down Alarm/
↓
+ Scale/
↑
buttons at once for 3 seconds or more.
To Modbus Setting Mode
Hold down Alarm/
↓
+ Shift buttons at once for 3 seconds or more.
To Infrared Communication Mode
Hold down Alarm/
↓
+ Up buttons at once for 3 seconds or more.
To Lockout Setting Mode
Hold down Max/Min + Alarm/
↓
buttons at once for a preset time duration.
To Loop Test Output
Hold down Alarm/
↓
+ Scale/
↑
+ Shift buttons at once for 5 seconds or more.
■
TRANSITION FROM EACH MODE TO MEASURING MODE
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.
Measuring
Mode
Lockout Setting Mode
POWER ON
Alarm Setting Mode
Advanced Setting Mode
Hold down Alarm/
↓
or Scale/
↑
for ≥ 1 sec.
Hold down Scale/
↑
for ≥ 3 sec.
Scaling Setting Mode
for ≥ 3 sec.
Hold down Alarm/
↓
at once for ≥ 3 sec.
Hold down Alarm/
↓
+ Shift
for ≥ 1 sec.
Hold down
Alarm/
↓
or Scale/
↑
at once for a preset
time duration
Hold down Max/Min + Alarm/
↓
for ≥ 1 sec.
Hold down
Alarm/
↓
or Scale/
↑
Hold down Alarm/
↓
or Scale/
↑
for ≥ 1 sec.
Hold down Alarm/
↓
+ Scale/
↑
+ Shift
Loop Test Output Mode
May be disabled depending on the
model suffix codes.
Indicated regardless of the model
suffix codes.
at once for ≥ 5 sec.
for ≥ 1 sec.
Hold down
Alarm/
↓
or Scale/
↑
for ≥ 1 sec.
Hold down
Alarm/
↓
or Scale/
↑
Modbus Setting Mode
Infrared Communication Mode
at once for ≥ 3 sec.
Hold down Alarm/
↓
+ Up
Hold down Alarm/
↓
or Scale/
↑
for ≥ 1 sec.
at once for ≥ 3 sec.
Hold down Alarm/
↓
+ Scale/
↑